Mutual Inductance Model of the Mechanical Stress Sensitivity of the Power Transformer Functional Parameters
DOI:
https://doi.org/10.14313/JAMRIS/4-2024/28Keywords:
mutual inductance model, magnetoelastic effect, electricl steelAbstract
The mutual inductance model enables testing the behavior of power transformers under different operation conditions, especially under the environmental influences on the transformer’s core. This paper presents the investigation results of the stress dependence of the magnetic relative permeability of the power transformer. It was observed that under tensile mechanical stresses up to 98 MPa applied to the core, the transformer input current amplitude increases by almost 67%, whereas the transformer's reactive power increases by 53%. In industrial systems, such changes can potentially lead to unwanted power system shutdowns due to overloading. This effect should be considered during the development of critical power systems.
Downloads
Published
Issue
Section
License
Copyright (c) 2024 Journal of Automation, Mobile Robotics and Intelligent Systems

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.